IPN = 100..1000 A
AC/DC Current transducer DHR-C10
The transducer for the electronic measurement DC & distorted AC
waveforms current, with galvanic isolation between the primary (High
power) and the secondary circuits (Electronic circuit). True RMS 0-10V
voltage output.
Electrical data
Primary Nominal
DC & AC Current
I PN (A.t.RMS)
Primary AC Current
Max. Peak Value
I P (A)
Analogue Output
Signal
V OUT (VDC)
600
600
1000
1000
1800
1800
1800
0-10
0-10
0-10
0-10
0-10
0-10
0-10
100
200
300
400
500
600
1000
RL
VC
IC
Load resistance
Supply voltage
Current Consumption
Limitation of voltage output (0-10V)
Overloaded input current (Ampere Turns)
Features
Type
DHR 100 C10
DHR 200 C10
DHR 300 C10
DHR 400 C10
DHR 500 C10
DHR 600 C10
DHR 1000 C10
≥ 10
kΩ
+20 .. 50 V DC
30
mA
< 14
V
30000
A.t
X
L
VOE
VOT
TCε G
tr
f
Accuracy @ IPN, TA = 25°C (without offset)
Linearity (1% of IPN .. ± IPN)
Electrical offset voltage, TA = 25°C
Thermal drift of VOE (-20..+60 °C)
(-40..+70 °C)
Thermal drift of the gain (% of reading)
Response time @ 90% of IP
Frequency bandwidth (±1%)
< ±1
% of IPN
< ±1.0 % of IPN
< ±1.0 % of IPN
±1
mV/K
±2.0
mV/K
±0.1
%/K
< 150
ms
DC 20..6000Hz
General data
TA
TS
m
Ambient operating temperature
Ambient storage temperature
Mass
Protection type
UL94 classification
• True RMS output
• Panel mounting
• Eliminates insertion loss
Advantages
• Large aperture for cable up to
Ø32mm
• High isolation between primary and
secondary circuits
• Easy to mount
Accuracy-Dynamic performance data
ε
• VFD and SCR waveforms current
measurement
-40 .. +70
-40 .. +85
260
IP20
V0
°C
°C
g
Applications
• VFD Controlled Loads:
VFD output indicates how the motor
and attached load are operating.
• SCR Controlled Loads:
Acurate measurement of phase
angle fired or burst fired (time
proportioned) SCRs. Current
measurement gives faster
response than temperature
measurement.
• Switching Power Supplies and
Electronic Ballasts:
True RMS sensing is the most
accurate way to measure power
supply or ballast input power.
Notes : Installation and maintenance should be done with power supply disconnected.
The operator must have accrediation to install this material.
The users must take care of all protection gurantee against electrical shock.
050526/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Components
Page 1/3
www.lem.com
Current Transducer DHR-C10
Isolation characteristics
Vb
Rated Voltage
1000
V
with IEC 61010-1 acc. to the 61326 standards and following conditions :
- Single insulation
- Over voltage category CAT III
- Pollution degree PD2
- None uniform field
R.m.s. voltage for AC insulation test, 50Hz, 1min
5
kV
Creepage distance
11
mm
Clearance distance
11
mm
Comparative tracking index (Group I)
600
Vd
dCp
dCl
CTI
Notes :
Output polarity with DC input
Output in V
10
-Ipn
0
+Ipn
050526/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Components
Page 2/3
www.lem.com
Dimensions DHR-C10 (in mm. 1 mm = 0.0394 inch)
25
70
32
4.
60
70
60
40
10
6.8 0
15
25
2 2.2 8
8.30
6 .80
4 .60
33 .80
2 .50
90
4
7
6
78
Connections
Mechanical characteristics
• Wires up to 2 mm ∅
• General tolerance
• Primary aperture
±1 mm
∅ 32.0 mm
• Panel mounting
• Distance between holes
4 holes ∅ 4.6 mm
70.0 mm & 78 mm
DHR
(see above dimensions)
For panel mounting, replace M4 screws by new one (not supplied)
Output Connector
1(+) 2(none) 3(out) 4(GND)
with appropriate length to panel´s thickness.
24 VDC Power
Safety
(+)
(-)
10k
(-)
This transducer must be used in electric/electronic equipment
with respect to applicable standards and safety requirements
in accordance with the following manufacturer's operating
instructions.
(+)
Load
(Controller, meter etc)
+24VDC
Is
OUT
Ip
GND
Caution, risk of electrical shock
When operating the transducer, certain parts of the module can
carry hazardous voltage (eg. primary busbar, power supply).
Ignoring this warning can lead to injury and/or cause serious
damage.
This transducer is a built-in device, whose conducting parts
must be inaccessible after installation.
A protective housing or additional shield could be used.
Main supply must be able to be disconnected.
050526/4
LEM reserves the right to carry out modifications on its transducers, in order to improve them, without previous notice.
LEM Components
Page 3/3
www.lem.com